Assessment of university classroom ventilation during the COVID-19 pandemic
Abstract
Ventilation plays an important role in mitigating the risk of airborne virus transmission in university classrooms. During the early phase of the COVID-19 pandemic, methods to assess classrooms for ventilation adequacy were needed. The aim of this paper was to compare the adequacy of classroom ventilation determined through an easily accessible, simple, quantitative measure of air changes per hour (ACH) to that determined through qualitative "expert judgment" and recommendations from the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE), and the American Conference of Governmental Industrial Hygienists (ACGIH)®. Two experts, ventilation engineers from facilities maintenance, qualitatively ranked buildings with classrooms on campus with regard to having "acceptable classroom ventilation." Twelve lecture classrooms were selected for further testing, including a mix of perceived adequate/inadequate ventilation. Total air change per hour (ACH) was measured to quantitatively assess ventilation through the decay of carbon dioxide in the front and rear of these classrooms. The outdoor ACH was calculated by multiplying the total ACH by the outdoor air fraction. The classrooms in a building designed to the highest ASHRAE standards (62.1 2004) did not meet ACGIH COVID-19 recommendations. Four of the classrooms met the ASHRAE criteria. However, a classroom that was anticipated to fail based on expert knowledge met the ASHRAE and ACGIH criteria. Only two classrooms passed stringent ACGIH recommendations (outdoor ACH > 6). None of the classrooms that passed ACGIH criteria were originally expected to pass. There was no significant difference in ACH measured in the front and back of classrooms, suggesting that all classrooms were well mixed with no dead zones. From these results, schools should assess classroom ventilation considering a combination of classroom design criteria, expert knowledge, and ACH measurements.
Part of CIRS Nexus · Curated by Lauren Lowenstein, The Biotoxin Lady
Related Papers
- Misalignment between Clinical Mold Antigen Extracts and Airborne Molds Found in Water-damaged HomesAnnals of the American Thoracic Society · 2021 · 1 shared tag
- Microbiological Analysis of Indoor Air in Selected Primary Schools: Health Concerns and RecommendationsJournal of Multidisciplinary Science MIKAILALSYS · 2023 · 1 shared tag
- Exposures in the Indoor Environment and Prevalence of Allergic Conditions in the United States of AmericaInternational Journal of Environmental Research and Public Health · 2021 · 1 shared tag
- Dampness, mould, onset and remission of adult respiratory symptoms, asthma and rhinitisEuropean Respiratory Journal · 2019 · 1 shared tag
- Impact of Epidemic Intelligence Service Training in Occupational Respiratory EpidemiologyATS Scholar · 2023 · 1 shared tag
- Streptomyces albireticuli lung infection managed as a pulmonary air cyst: a case report and literature reviewFrontiers in Cellular and Infection Microbiology · 2024 · 1 shared tag